QUALITROL – 509 Temp Monitor

This advanced transformer monitor provides real-time diagnostics and predictive analytics for oil-filled systems. Features up to 16 fiber optic inputs, cooling control, and a TransLife dashboard for asset tracking.

Giá: Liên hệ

Advanced transformer monitor for medium and large transformers, offering real-time diagnostics, control, and predictive analytics for oil-filled transformer systems.

  • Up to 16 input channels and 16 fiber optic inputs
  • 8 output relays for control and alarms
  • TransLife dashboard for asset life tracking
  • Temperature Profiler and Critical Forecast tools
  • Advanced cooling control with seasonal and ambient adjustments
  • Data logging for up to 20 parameters
  • Real-time comparison of direct and calculated winding temperatures
  • Factory-calibrated and tested for reliability
  • Mounting: panel, rack, fiberglass, steel, stainless steel
  • Communication: RS-232, RS-485, Ethernet, USB
  • Protocols: MODBUS, DNP3.0, IEC 61850, ASCII
  • Expansion modules for up to 16 inputs
  • Integration with RPRR, pressure, oil level, fiber optics, and flow sensors

Electrical

Input Power Universal
Power Consumption < 35 Watts
Number of Inputs Accepts up to 8 input modules of various, configurable types
Winding Temperature Simulation Uses clamp-on sensor
Output Type Form C, 10 amps @ 120/240 VAC, 10 amps @ 30 VDC
Dielectric Strength 2500 VAC, 60 seconds to ground

Mechanical

Mounting Style
  • ENCLOSURE
  • Panel Mount

Other

Warranty 5 Years

User Interface

Control 8 pushdown buttons located on front panel
Display 2 x 16 character backlit LCD

Communications

Number of Output Relays 8 programmable, 1 system status , 1 relay for heater control
Communication Protocols DNP 3.0 level 1 slave, Modbus RTU, ACII, IEC 61850, IEC 60870

Data Logging

Number of Parameter Points Logs up to 20 parameters
Log Rate Selectable from one minute to 24 hours

 

  • Vault transformers
  • Large distribution transformers
  • Medium and large power transformers
  • Load tap changers
  • Non-transformer applications requiring temperature and pressure monitoring